FX communication
RS instruction 9
9-12
4 ) Use interlink mode of control line
*1 While the counterpart equipment is ready to receive, turn ON the DR (DSR) signal.
While both the DR (DSR) signal and the send request are turned on, the FX
2N
sends the data.
*2 In the interlink mode, the programmable controller turns OFF the ER (DTR) signal before the
30th character receive buffer limit, and requests the counterpart equipment to stop send.
After this send request, up to 30 characters can be received. The 31st and later characters
cannot be received. Stop send temporarily, then send the remaining data after the ER (DTR)
signal is turned ON again.
When send is stopped, receive is completed after the time-out evaluation time is expired.
When send is not stopped, receive is completed after the final character of the send data is
received or the 30th character is received. Therefore, receive points need to set 30th or more.
*3 Reset using a sequence program.
If it is turned ON, the next data cannot be received.
In the interlink mode, make sure to set the number of receive points to 30 characters or more.
Reset it using a program.
When it is not trurned off,
the next data cannot be
received.
Data 2
RS instruction
driving
Send data
SD (TXD)
OFF ON
Data 4
OFFON
Send request
M8122
Receive
completion
M8123
Data 4
Data 1 Data 3
Receive data
RD (RXD)
OFF ON
*1 *1 *1
Data 3
*3
Time-out
evaluation time
D8129
×
10ms
OFF ON ON ON
Reset using a program.
When it is not trurned off, the
next data cannot be received.
OFFON
DR(DSR)
Time-out
evaluation
flag M8129
Up to 30 characfers can be
received *2
ER(DTR)